Scimitar

scimitar 2k power inverter

Product Information

The SCIMITAR Series are 1kVA and 2kVA inverters which are 19” rack-mountable and only 1RU high. They operate from a 12V, 24V or 48VDC source and produce a 115 or 230VAC output.

The tightly regulated low distortion 50 or 60Hz sine wave is produced by DSP controlled power circuits using an advanced high frequency, pulsewidth modulation technique which achieves up to 92% efficiency.
A built-in Static Transfer Switch allows connection of a utility or other AC power source which can be switched to the load automatically in the event that the inverter switches off.
In normal operation these inverters isolate the load from wide voltage swings , transients and noise usually present in the AC utility and which can cause equipment reliability problems.
Output voltage and frequency are programmable from the front panel, as well as Baud Rate for the RS232 communications interface which can be used for remote monitoring.

TWO YEAR WARRANTY

Features and Options
  • 19-Inch x 1UR Rack Mounting
  • 1000 or 2000 VA Output Capacity
  • 115VAC or 230VAC Output
  • 50 or 60Hz Low Distortion Sine Wave
  • 12, 24 or 48VDC Input
  • -20 to +60C Operating Temperature Range
  • Static Transfer Switch Built-in
  • Programmable Output Voltage and Frequency (Front panel DIP switch)
  • Powers Reactive Loads
  • LED Status Display
  • Relay Alarm Output
SPECIFICATIONS
 
INPUT
Voltage

12VDC (10-16VDC)
24VDC (20-32VDC)
48VDC (42-62VDC)

Current (max.) 1kVA Models
98.8A @ 12V
48.5A @ 24V
22.8A @ 48V
2kVA Models
186.1A @ 12V
95.6A @ 24V
45.0A @ 48V
 
OUTPUT
Voltage

100/110/115/120VAC ±3% (switch selectable)
200/220/230/240VAC ±3% (switch selectable)

Power See model table opposite
Frequency 50Hz or 60Hz ±0.05% (switch selectable)
Efficiency 86-92% depending on model
Peak Output Current 1kVA Models
15A @ 120VAC
9A @ 230VAC

2kVA Models
25A @ 120VAC
11A @ 230VAC
Output Waveform Pure Sine Wave <3% THD (R Load)
 
TRANSFER FUNCTION (-STS OPTION)
AC Input Range90 - 130VAC (110VAC nominal)
180-260VAC (230VAC nominal)
Frequency 47-63Hz
Transfer Time 4-6mS
Alarm Relay Form-C dry contacts, indicates presence of AC Utility supply
 
OTHER TECHNICAL DATA
Protection Output Overload; Output Short Circuit; Input Reverse Polarity (fuse); Input Undervoltage; Input Overvoltage; Over Temperature
Alarms General alarm signal activated by an open photo-relay if in fault mode, available at rear signal connector
Display OVP - UVP - OTP - OLP - VAC - AMP - WATT - VDC - TEMP - Hz
Control Port RS232C - Baud Rates - 2400, 4800, 9600, 19200 (switch selectable)
SNMP (Option) Operates in conjunction with NetAgent UPS SNMP Agent
Temperature Range Operating: -20°C to +60°C
Storage: -30°C to +70°C
MTBF > 98,000 hrs @ 25°C ambient, nominal output voltage & full load
 
DESIGN STANDARDS
Safety 120VAC Models: UL60950-1 (Listed - E130645)
230VAC Models: EN60950-1
EMC 120VAC Models: FCC Class B
230VAC Models: EN 55022:1998/ A1:2000/A2:2003(Class B) | EN 55024: 1998/ A1:2001/A2:2003 | EN 61000-3-2:2000/A2: 2005 | EN 61000-3-3:1995/A1: 2001 | IEC 61000-4-2:1995/ A1:1998/A2:2000 | IEC 61000-4-3:2002/A1:2002 | IEC 61000-4-4:2004 | IEC 61000-4-5:1995/A1:2000 | IEC 61000-4-6:1996/A1:2001 | IEC 61000-4-8:1993/A1:2000 | IEC 61000-4-11:2004
 
MECHANICAL
Dimensions, inches (mm) 19 (484) W x 1.73 (44.0) H x 16.1 (408.7) D
Weight19.8lbs / 9Kg
Mounting 19" Rack, 1RU
STANDARD MODELS
Model
Number
Output
Power 4
Output
Voltage 1, 2, 3
Input
Voltage
SNMP 6
INV1210R-N 5 1kVA @ 0.85PF
850W @ 1.0PF
115VAC 12VDC Option
INV2410R-N 5 24VDC Option
INV4810R-N 5 48VDC Option
INV1210RH-E 230VAC 12VDC Option
INV2410RH-E 24VDC Option
INV4810RH-E 48VDC Option
INV1220R-N 5 2kVA @ 0.85PF
1600W @ 1.0PF
115VAC 12VDC Option
INV2420R-N 5 2kVA @ 0.85PF
1700W @ 1.0PF
24VDC Option
INV4820R-N 5 48VDC Option
INV1220RH-E 2kVA @ 0.80 PF
1600W @ 1 PF
230VAC 12VDC Option
INV2420RH-E 2kVA @ 0.85 PF
1700W @ 1 PF
24VDC Option
INV4820RH-E 48VDC Option
Notes:
  1. 115VAC models are shipped pre-programmed to 60Hz.
    230VAC models are shipped pre-programmed to 50Hz.
  2. 115VAC models can be programmed to 100, 110, 115 or 120VAC.
    230VAC models can be programmed to 200, 220, 230 or 240VAC.
  3. 115VAC models have 2 x NEMA 5-15 outlet sockets.
    230VAC models have 2 x IEC60320-C13 outlet sockets.
  4. If in doubt about load PF (Power Factor) assume that it is 1.0PF.
  5. These models are UL Listed, file number E130645.
  6. To specify the SNMP option add ‘S’ to the end of the model number, e.g. INV4810R-NS.