1U Fixed DC Breaker Panel


Product Information
DPB1U Series 1U DC breaker panel provide distribution and overload protection for 1 to 12 circuits. The panels are only one mounting position (1.75 inches) high.
The panel provides 1 to 12 single-bus breakers or 2 to 12 dual-bus (A&B) breakers (1 to 6 per bus) and distributes up to a total of 300 amperes of load current from two separate 150-ampere sources with true A and B distribution and alarm capabilities.
A and B sections of the dual-bus 1u dc breaker panel are isolated and can be separately configured for 12, 24 or 48 volts and are polarity neutral.
Breaker capacities are from 1 to 50 amperes. Alarms are indicated by a dual-color LED (green/red) and one Form C relay contact per bus.
The 1u dc breaker panels come with brackets that permit mounting in either a 19- or 23-inch relay rack. They can be mounted from the front of the rack with offsets every quarter-inch front to back to align with existing rack-mounted equipment.
Features and Options
- One Mounting Position High: 1.75″
- 19- or 23-Inch Rack Mounting
- Magnetic Circuit Breakers
- Single Bus with 1 to 12 Breakers
- Dual Bus (A/B) with 1 to 6 Breakers each side
- Voltage: 12, 24 or 48VDC
- POLARITY NEUTRAL
- A & B are Isolated Loads
- A & B Can Be Separately Configured
- 1A to 50A per Breaker
- Bus Capacity: 150A per Bus
- Green/Red LED Breaker Alarm
- Two Form C Relay Contacts per Bus (A/B)
- Rack Offset Every ¼” from Front to Back
- Fail Safe Option
- Circuit Breaker Panels
SPECIFICATIONS
|
|
---|---|
INPUT / OUTPUT | |
Panel Capacity | see model table opposite |
Configuration | Single Bus: 1 to 12 Breakers Dual Bus: 1 to 6 Breakers Each |
Breaker Capacity | 1A to 50A |
Voltage | 48V Nominal: 42-60VDC 24V Nominal: 21-30VDC 12V Nominal: 10.5-15VDC |
Polarity | POLARITY NEUTRAL |
ALARMS | |
Alarm Indicator | Dual-Color LED Per Bus |
LED Status Indication | Green = Normal Red = Alarm Off = No Power |
Alarm Connections | One Form C Relay Contact Per Bus |
SAFETY STANDARDS | |
Certifications | UL69950-1 2nd Ed.,CAS22.2 No.950-1 2nd Ed., EN60950-1 2nd Ed. |
ENVIRONMENTAL | |
Operating Temp. Range | -10°C to +70°C |
Storage Temp. Range | -40°C to + 85°C |
Humidity | 0% to 95%, Non-Condensing |
PHYSICAL | |
Case Material | Steel |
Finish | Powder Coat Black |
Dimensions, Inches (mm) | 1.75 (44.5) H x 19.00 (483) W x 9.00 (229) D [10.44 (265mm) D with option F] |
Weight | 10.30 lbs. ( 4.67 kg.) |
Rack Mounting Width | 19 or 23 Inches using reversible mounting brackets |
STANDARD MODELS | ||||
---|---|---|---|---|
Model Number | Input Feeds | Max. No. Breakers | Amps Each Bus | Total Amps |
DPB1U-Axy-C | 1 | 6 | 150 | 150 |
DPB1U-Axy-Bxy-C-S | 1 | 12 | 150 | 150 |
DPB1U-Axy-Bxy-C | 2 | 6 EACH BUS | 150 | 300 |
Note: ‘x’ denotes the operating voltage where 1=48V, 4=24V and 6=12V. ‘y’ denotes between one and six breakers which must be specified as part of the final model number. See ordering guide on datasheet to specify a full model number. |