2U DC Breaker Panel


Product Information
DPP2U Series 2u dc distribution panels provide distribution and overload protection for 1 to 20 circuits with circuit breakers that can be field installed/exchanged using a supplied puller tool.
UNIPOWER’s DPP2U Series circuit breaker panels provide distribution and overload protection for 1 to 20 circuits with circuit breakers that can be field installed/exchanged using a supplied puller tool. The panels are only two mounting positions (3.5 inches) high.
The dual-bus model provides up to 20 breakers 900A (10A/10B) distribution and alarm capabilities. The A and B sections are fully isolated from each other and are polarity neutral. Breaker capacities range from 2.5 to 200 amperes. A single-bus 450A model is also available.
Breaker and power fail alarms are indicated by a dual color LED (green/red) and Form C relay contacts for each bus.
Rear accessed load cables connect via 2-hole anti-rotation posts. All connections are straight on for easy installation.
Three Year warranty
Features and Options
- 48/24V Dual Voltage
- POLARITY NEUTRAL
- 450A bus bar inputs (900A total)
- Dual Feed (optional Single Feed)
- “Mid-Trip” circuit breaker function
- Circuit Breaker ‘puller’ included
- Tapered entry for easy insertion
- NO or NC alarm contacts
- Alarm LEDs
- Power Fail form-C alarm
- 19″ & 23″ universal mounting brackets
- Rear panel safety cover standard
SPECIFICATIONS
|
|
---|---|
INPUT | |
Voltage Range | 20-60VDC |
Current Capacity | 450A per Bus @ 35°C 400A per Bus @ 40°C 320A per Bus @ 50°C |
OUTPUT | |
Voltage Range | 20-60VDC |
Breaker Capacity | See Table |
Alarm Indicator | Dual Color LED each Bus – Green = Normal, Red = CB Trip, Off = No Power |
Alarm Relays | One Form C Contact for each Bus |
ENVIRONMENTAL | |
Operating Temp. Range | -10ºC to +70ºC |
Storage Temp. Range | -40ºC to + 85ºC |
Humidity | 0% to 95%, Non-Condensing |
Altitude | 10,000 feet |
PHYSICAL SPECIFICATIONS | |
Case Dimensions, Inches (mm) | without Plastic Safety Cover – 3.45 H x 17.16 W x 9.48 D (87.6 x 435.9 x 240.8) with Plastic Safety Cover – 3.45 H x 17.16 W x 14.08 D |
Rack Mounting Width | 19 or 23 Inches |
Weight | 12.5 lbs. ( 5.67 kg.) |
DUAL FEED CONFIGURATION | |||||
---|---|---|---|---|---|
MODEL NUMBER | VOLTS EACH FEED | INPUT FEEDS | MAX. # BREAKERS | AMPS EACH FEED | TOTAL AMPS |
DPP2U-A1-B1 | 48/24 – 48/24 | 2 | 10 A side & 10 B side | 450 | 900 |
SINGLE FEED CONFIGURATION | |||||
---|---|---|---|---|---|
MODEL NUMBER | VOLTS EACH FEED | INPUT FEEDS | MAX. # BREAKERS | AMPS EACH FEED | TOTAL AMPS |
DPP2U-A1-B1-S | 48/24 | 1 | 20 | 450 | 450 |
AVAILABLE BREAKERS | ||||
---|---|---|---|---|
Breakers need to be ordered individually and are shipped with each panel as separate items for field installation.
Breakers rated 125A to 200A require two positions and are supplied as a kit with output bus paralleling bars. See datasheet for details of the approved types of breakers. |