Scimitar 3000


Product Information
The SCIMITAR 3000 Series are 3000 watt inverters which are 19” rack-mountable and only 2RU high. Different models operate from a 12, 24 or 48 VDC source and produce a sine-wave 115 or 230 VAC output.
The tightly regulated low distortion 50 or 60Hz sine wave is produced by DSP controlled power circuits using an advanced high frequency, pulse-width modulation technique which achieves up to 92% efficiency.
A built-in Static Transfer Switch allows connection of a utility or other AC power source which can be switched to the load automatically in the event that the inverter switches off.
In normal operation these inverters isolate the load from wide voltage swings , transients and noise usually present in the AC utility and which can cause equipment reliability problems.
Output voltage and frequency are programmable from the front panel, as well as Baud Rate for the RS232 communications interface which can be used for remote monitoring.
Three Year warranty
Features and Options
- 19-Inch x 2RU Rack Mounting
- 3000W Output Capacity
- 115VAC or 230VAC Output
- 50 or 60Hz Low Distortion Sine Wave
- 12, 24 or 48 VDC Input
- -20 to +50°C Operating Temperature
- Static Transfer Switch Built-in
- Adjustable Output Voltage
- Programmable Frequency (DIP switch)
- Powers Reactive Loads
- LED Status Display
- Relay Alarm Output
SPECIFICATIONS
|
|
---|---|
INPUT | |
Voltage | 12VDC (10-16VDC) 24VDC (20-32VDC) 48VDC (42-62VDC) |
Current (max.) | 349A @ 12V 171A @ 24V 81A @ 48V |
OUTPUT | |
Voltage | 100-120VAC (adjustable) 200-240VAC (adjustable) |
Power | 3000W continuous | 6000W peak |
Surge Rating | 3200W for 3 minutes, 3500W for 3 seconds |
Frequency | 50Hz or 60Hz ±0.05% (switch selectable) |
Efficiency | 86-92% depending on model |
Output Waveform | Pure Sine Wave <3% THD (R Load) |
TRANSFER FUNCTION (-STS OPTION) | |
AC Input Range | 90-130VAC (110VAC nominal) 180-260VAC (230VAC nominal) |
Frequency | 47-63Hz |
Transfer Time | 4-6mS |
Alarm Relay | Form-C dry contacts, indicates presence of AC Utility supply |
OTHER TECHNICAL DATA | |
Protection | Output Overload; Output Short Circuit; Input Reverse Polarity (fuse); Input Undervoltage; Input Overvoltage; Over Temperature |
Alarms | General alarm signal activated by an open photo-relay if in fault mode, available at rear signal connector |
Display | OVP – UVP – OTP – OLP – VAC – AMP – WATT – VDC – TEMP – Hz |
Control Port | RS232C – Baud Rates – 2400, 4800, 9600, 19200 (switch selectable) |
SNMP (Option) | Operates in conjunction with NetAgent UPS SNMP Agent |
Temperature Range | Operating: -20°C to +50°C Storage: -30°C to +70°C |
MTBF | > 98,000 hrs @ 25°C ambient, nominal output voltage & full load |
DESIGN STANDARDS | |
Safety | EN60950-1 |
EMC | 120VAC Models: FCC CFR Title 47 Part 15 Subpart B: 2008 Class A CISPR 22: 2005 ANSI C63.4: 2003230VAC Models: EN55022:2006+A1: 2007, Class A EN55024: 1998+A1: 2001+A2: 2003 EN61000-3-2: 2006 EN61000-3-3: 1995+A1: 2001+A2: 2005 IEC61000-4-2 Ed. 1.2: 2001-04 IEC61000-4-3 Ed. 3.0: 2006 IEC61000-4-4: 2004 IEC61000-4-5 Ed. 2.0: 2005 IEC61000-4-6 Ed. 2.2: 2006 IEC61000-4-8 Ed. 1.1: 2001-03 IEC61000-4-11 2nd Ed.: 2004-03 |
MECHANICAL | |
Case Dimensions, inches (mm) | 16.7 (424) W x 3.5 (88) H x 17.5 (445) D |
Weight | 31.5lbs / 14.3Kg |
Mounting | 19″ Rack, 2RU |
STANDARD MODELS | |||||
---|---|---|---|---|---|
Model Number |
Output Power |
Output Voltage 1, 2 |
Input Voltage |
SNMP 3 | |
INV1230R-B | 3kW – Continuous 6kW – Peak |
115VAC | 12VDC | Option | |
INV2430R-B | 24VDC | Option | |||
INV4830R-B | 48VDC | Option | |||
INV1230RH-B | 230VAC | 12VDC | Option | ||
INV2430RH-B | 24VDC | Option | |||
INV4830RH-B | 48VDC | Option | |||
Notes:
|