Aspiro 1U

Aspiro 1U

AVAILABLE IN NORTH AMERICA ONLY

Product Information

Aspiro 1U is a compact 1RU high 19/23” or ETSI rack-mounted, integrated 45 Amp DC power system providing an output of -48VDC.

The Aspiro 1U 45 amp DC power system can accommodate 1 or 2 Aspiro family high efficiency hotswap rectifiers. A total load + charge current of 45A / 2.4kW is available. The rectifiers are internally fan cooled with speed control which is a function of load and temperature, keeping acoustic noise to a minimum.

The DC output circuits can provide up to 4 loads with breakers rated from 1A to 30A. An additional breaker provides battery protection. A programmable low voltage battery disconnect (LVD) is standard.

Three Year warranty
Features and Options
  • 95% Efficiency Rectifiers
  • 45A / 2.4kW Capacity
  • Intelligent Battery Management
  • Remote Monitoring & Control
  • Field Replaceable Controller
  • Ethernet Comm. with SNMPv3
  • 3 LED Alarm/Status Indicators
  • 4 Form-C Relay Alarms
  • 4 Load Breakers
  • 1 Battery Breaker
  • LCD Display/Touchpad
SPECIFICATIONS
OUTPUT
System Voltage -48VDC nominal | -53.5 float (factory default setting, user adjustable)
Maximum Power 1600W @ 120VAC
2400W @ 230/400VAC
Maximum Capacity @ 120VAC nominal Load – 25A
Battery – 25A discharge | s/w controlled
Maximum Capacity @ 230/400VAC nominal Load – 45A
Battery – 45A discharge | s/w controlled
No. Rectifier Slots 2
DC DISTRIBUTION
Load Circuits 4 x Breakers 1A to 30A
Battery Circuits 1 x 40A to 65A
INPUT
Voltage (nominal) 1-phase 100-120/200-240VAC (L + N + PE)
2-phase 100-120/200-240VAC (L + N + PE)
Frequency 47-63Hz
Maximum Input Current 1-phase – 16A
2-phase – 8A each input
Rectifier Power Factor >0.98 (typical)
MONITORING & CONTROL (ACX Advanced Controller)
Alarm Relays 4
Local Interface 4 x 20 LCD, 4-key menu, USB / RS232, microSD card slot (4GB max,) for data logging
Remote Interface Ethernet / Modem using PowComª software package
Ethernet port allows monitoring and control over a TCP/IP network.
Web browser support + SNMPv3.
LED Indications Green – System ON; Yellow – Message(s); Red LED – Alarm(s)
External Digital I/O 2 x Inputs, 2 x Outputs (Open Collector)
BATTERY MANAGEMENT
Symmetry Inputs 6 or 12 (can be redefined as analog inputs up to 100VDC)
Low Voltage Battery Disconnect (LVBD) 1 x 80A Programmable
Temperature Compensated Charging Programmable
COMPLIANCE
EMC EN 300 386 ; EN61000-6-3 (Emission)
EN61000-6-2 (Immunity)
Safety CAN/CSA C22.2 No 62368-1:2014
UL 62368-1:2014
EN 62368-1:2014/A11:2017
ENVIRONMENTAL
Operating Temperature -40°C to +55°C
Storage Temperature -40°C to +85°C
DIMENSIONS, ins. (mm)
19/23″ Mounting 19/23 (483/584) W x 1.7 (44) H x 10.4 (265) D
ETSI.21″ Mounting 21.1 (535) W x 1.7 (44) H x 10.4 (265) D
INTELLIGENT BATTERY MANAGEMENT
(PROVIDED VIA ACX ADVANCED CONTROLLER)
Battery Disconnection Provides voltage controlled disconnection of batteries.
Boost Charging Manual time controlled or automatic boost charging with adjustable time and voltage levels.
Battery Tests Automatic or manual testing of batteries up to six times per year with a 10 test memory. Variables include test duration and end voltage.
Battery discontinuance test to ensure battery connection.
Enhanced Battery Monitoring Monthly logging of essential battery parameters including temperature, temperature hours, current, charging voltage and symmetry voltage, data logged for 5 years.
Site Logs System tools developed to assist site management. Daily peak load and statistic logs available.
Symmetry Measurement Optional tool that measures batteries for early detection of thermal runaway.
Temperature Compensation Charging Allows continuous adjustment of output voltage according to battery temperature.
Features include adjustable compensation factor and separate thresholds for high temperature alarms.
STOCK MODELS (normally held in stock for immediate delivery)
ORDER CODE DESCRIPTION
M00035*900041 Single Feed (1-phase)
ACX Controller
65A Battery Breaker
Load Breakers: 30A/20A/15A/10A
19/23” Mounting Brackets
3m Temp. Sensor Cable (x1)
3m Symmetry Cable (x1)[Rectifiers & blanking modules must be ordered separately.]
M00035*900018 Dual Feed (2-phase)
ACX Controller
65A Battery Breaker
Load Breakers: 25A/20A/15A/10A
19/23” Mounting Brackets
3m Temp. Sensor Cable (x1)
3m Symmetry Cable (x1)[Rectifiers & blanking modules must be ordered separately.]
XR08.48G
XPGe12.48G
XB-01-G
17A/800W Rectifier Module
25A/1200W Rectifier Module
Blanking Module
For complete details see the datasheet.