Sageon II

Sageon II
Sageon
System Datasheet
48V System Manual
24V System Manual
SageView Software Manual
SageView Win 8/8.1 USB Driver Manual
48V Rectifier Datasheet
24V Rectifier Datasheet
SageNET Manual
SageNET-3 (SNMP) Manual
WEBCSU-3 Datasheet
WEBCSU-3 Manual
Battery Monitor Datasheet
Battery Monitor Manual
Sageon Site Monitor Datasheet
Sageon Site Monitor Application Note

Product Information
The SAGEON II Power Module 600Amp Bulk DC Power System is available in two bulk power sizes 600A (N+1) and 400A (N+1), the Sageon II Power Module 600Amp Bulk DC Power System provides the flexibility to put power where it is needed.
The Sageon II Power Module 600Amp Bulk DC Power System consists of a power frame that includes the Sageon Controller and Rectifiers, mechanical mounting for up to nine rectifiers in the 400A offering and up to thirteen rectifiers in the 600A system. Each unit comes with an AC conduit box for ease of installation.
In addition to the basic control functions, the Sageon II Power Module 600Amp Bulk DC Power System supports all the advanced functionality available in all Sageon Family of products including: remote monitor and control, battery testing, individual cell monitoring, programmable battery recharge current, and site monitoring.
Three Year warranty
Features and Options
- High Power Density
- 400A or 600A Capacity
- 24VDC or 48VDC
- 2400W Hot-Swap Rectifiers
- Battery Testing
- Battery Monitoring
- Remote Monitoring & Control
- Programmable Battery Recharge
- Field Replaceable Controller
- LCD Display/Touchpad
SPECIFICATIONS
|
|
---|---|
INPUT | |
Voltage Range | AC 85-300VAC (L-N. 1ph, or 3ph-Y, 3ph-delta [option]. Fully protected up to 440VAC (L-N) |
Frequency | 47-63Hz |
Inrush Current | <16A RMS per rectifier |
THD | Line Harmonics meet EN61000-3-2 |
Power Factor | >0.98 for >50% output power |
OUTPUT | |
Voltage Range | -48VDC systems: adjustable range 42.0V to 59.5V +24VDC systems: adjustable range 21.0V to 30.0V |
Current Limit | -48VDC systems: 60A max. per rectifier, fully adjustable +24VDC systems: 50A max. per rectifier, fully adjustable |
Power Limit | -48VDC systems: 2400W per rectifier +24VDC systems: 1400W per rectifier |
Efficiency | >90% at 100% output power for 48VDC systems >88% at 100% output power for 24V systems |
Regulation | ±1% or better over line, load and temperature |
Noise | .1% pk-pk max. |
Line Regulation | <1mV RMS Psophometrically weighted <32dBrnC Voiceband <10mV RMS and <100mV peak-to-peak (10kHz-100MHz) |
PROTECTION | |
Short Circuit | Can sustain short circuit at output terminals indefinitely |
Reverse Battery Polarity | Internal fuse at output of RECTIFIER, integral battery circuit breakers and detection/disconnection circuitry |
High Voltage Shutdown | Rectifier shuts down if output exceeds programmed overvoltage limit |
Electrostatic Discharge (ESD) | IEC 61000-4-2 (Level 4: Air 15kV, Contact 8kV) |
AC Surge | IEC 61000-4-4 (EFT), Level 4 IEC 61000-4-5 (Impulse), Level X: 6kV/3kA IEC 61000-4-12 (Ringwave), Level X: 6kV/500A |
RF Immunity | IEC 61000-4-3 (Radiated), Level 4 IEC 61000-4-6 (Conducted), Level 3 |
RF Emissions | CISPR 22 Class B, (Conducted & Radiated) |
ENVIRONMENTAL | |
Operating Temp. Range | -40°C to +55°C (Full Load) |
Derating Operation | 50% power at +70°C |
Storage Temp. Range | -40°C to +70°C |
Humidity | 0 to 100% relative humidity, condensing |
Acoustic Noise | <60dB (A weighting) |
PHYSICAL SPECIFICATIONS | |
Dimensions, inches (mm) | 8.57-15.75 (222-400) H x 19.0 (483) W x 14.0 (355) D – see configurations table |
Weight | 81-127lb (37-58kg) – see configurations table |
COMPLIANCE | |
EMC | ETSI EN 300 386 V1.3.2 (2002-12) |
Safety | IEC 60950, UL/CSA 60950 |
Environmental | ETSI EN 300 019 |
STANDARD SYSTEM CONFIGURATIONS | |||||
---|---|---|---|---|---|
Type | Output Current |
Example | Height | Weight | |
List 40 | 400A | ![]() |
5RU | 81lb | 37kg | |
List 41 | 400A | ![]() |
7RU | 101lb | 46kg | |
List 60 | 600A | ![]() |
7RU | 107lb | 49kg | |
List 61 | 600A | ![]() |
9RU | 127lb | 58kg |