Guardian 5-7U M38


Product Information
Guardian Access M38 is a 5-7RU high 19” rack-mounted, integrated 600 Amp DC power system providing an output of -48VDC. These highly configurable systems incorporate 3 rectifier shelves with up to 11 Guardian family high efficiency hot-swap rectifiers.
Guardian Access M38 provides a maximum total current of 600A (N+1). This may be shared between the load and battery charge current, the latter being programmable via the controller. The rectifiers are internally fan cooled with speed control which is a function of load and temperature, keeping acoustic noise to a minimum. The DC distribution module in Guardian Access M38 can accommodate up to 20 pluggable breakers or TPS fuse modules. 4 or 8 of these in each case may be connected to the bus via the Low Voltage Battery Disconnect (LVBD).
Three Year warranty
Features and Options
- >96% Efficiency Rectifiers
- 60A to 600A (N+1) Capacity
- Remote Monitoring & Control
- Field Replaceable Controller
- Ethernet Comm. with SNMPv3
- 3 LED Alarm/Status Indicators
- 10 Form-C Relay Alarms
- Up to 20 Load Circuits
- 600A LVBD Standard
- LCD Display/Touchpad
- Easy Installation
SPECIFICATIONS
|
|
---|---|
OUTPUT | |
System Voltage | -48VDC nominal | -53.5 float (factory default setting, user adjustable) |
Maximum Capacity | Load – 600A Battery – 600A discharge | s/w controlled charge |
No. Rectifier Slots | 3 to 11 |
DC DISTRIBUTION | |
Load Circuits | Up to 20 (3A to 100A one position, 125A or 200A two position) |
Battery Circuits | 0, 4 or 8 x (100A one position, 125A two position or 200A two position) |
INPUT | |
Voltage (nominal) | 1-phase 200-240VAC (L + N + PE) |
Frequency | 47-63Hz |
Maximum Input Current | 17A per rectifier |
Rectifier Power Factor | >0.98 (typical) |
MONITORING & CONTROL (ACX Advanced Controller) | |
Alarm Relays | 10 standard |
Local Interface | 4 x 20 LCD, 4-key menu, USB / RS232, microSD card slot (4GB max,) for data logging |
Remote Interface | Ethernet / Modem using PowCom software package Ethernet port allows monitoring and control over a TCP/IP network. Web browser support + SNMPv3 |
LED Indications | Green – System ON; Yellow – Message(s); Red LED – Alarm(s) |
External Digital I/O | 2 x Inputs, 2 x Outputs (TTL Level) |
BATTERY MANAGEMENT | |
Symmetry Inputs | 6 or 12 (can be redefined as analog inputs up to 100VDC) |
Low Voltage Battery Disconnect (LVBD) | 1 x 600A Programmable |
Temperature Compensated Charging | Programmable |
COMPLIANCE | |
EMC | EN 300 386 ; EN61000-6-3 (Emission) ; EN61000-6-2 (Immunity) |
Safety | CAN/CSA C22.2 No 62368-1:2014 UL 62368-1:2014 EN 62368-1:2014/A11:2017 |
ENVIRONMENTAL | |
Operating Temperature | -40ºC to +55ºC |
Storage Temperature | -40ºC to +85ºC |
DIMENSIONS, ins. (mm) | |
Width | 19.0 (483) |
Height | 5RU, 6RU or 7RU |
Depth | 21.6 (548) overall | 14.0 (255) behind mounting plane |
INTELLIGENT BATTERY MANAGEMENT (PROVIDED VIA ACX ADVANCED CONTROLLER) |
|
---|---|
Battery Disconnection | Provides voltage controlled disconnection of batteries. |
Boost Charging | Manual time controlled or automatic boost charging with adjustable time and voltage levels. |
Battery Tests | Automatic or manual testing of batteries up to six times per year with a 10 test memory. Variables include test duration and end voltage. Battery discontinuance test to ensure battery connection. |
Enhanced Battery Monitoring | Monthly logging of essential battery parameters including temperature, temperature hours, current, charging voltage and symmetry voltage, Data logged for 5 years. |
Site Logs | System tools developed to assist site management. Daily peak load and statistic logs available. |
Symmetry Measurement | Optional tool that measures batteries for early detection of thermal runaway. |
Temperature Compensation Charging | Allows continuous adjustment of output voltage according to battery temperature. Features include adjustable compensation factor and separate thresholds for high temperature alarms. |
For more information, please visit the UNIPOWER Brand page for this product HERE